Wire Gauge (AWG) Calculator

Determine the minimum AWG cable size to prevent fire hazards and excessive voltage drop across DC and AC circuits.

🔌

Circuit Specifications

Amps
Feet

Recommended Wire Gauge

Recommended Cable Size
4 AWG
Actual Voltage Drop: 1.93% (0.23 Volts)
Voltage at Load
11.77 V
Terminal voltage delivered
Power Wasted in Wire
3.47 W
Dissipated as heat
Total Wire Resistance
0.0154 Ω
Allowed Drop Limit
0.36 V
Max allowed at 3%

Complete Guide to Wire Gauge Sizing & Voltage Drop

Selecting the appropriate wire gauge is a fundamental safety and performance requirement for any electrical installation. Undersized cables overheat, creating severe fire hazards, while excessive voltage drop starves terminal appliances, motors, and electronics of the operational voltage they require.

1. The Circular Mil Voltage Drop Formula

Electrical engineers calculate minimum conductor circular mil (CM) area using the standard formula:

Circular Mils = (2 × K × I × L) / Max Permissible Voltage Drop
  • K (Resistivity constant): 12.9 for Copper, 21.2 for Aluminum (at 75°C conductor operating temperature).
  • I: Continuous electrical current in Amperes.
  • L: One-way circuit length in feet.
  • Max Permissible Drop: Target voltage multiplied by maximum acceptable drop percentage.

2. NEC Standard Ampacity Reference Chart (Copper Conductor)

AWG SizeCircular MilsMax Continuous Amps (75°C)Standard Domestic Application
14 AWG4,11015 AmpsResidential general lighting & receptacles
12 AWG6,53020 AmpsKitchen small appliance circuits, bathrooms
10 AWG10,38030 AmpsElectric clothes dryers, 30A RV connections
8 AWG16,51050 AmpsElectric ranges, ovens, hot tubs
6 AWG26,24065 AmpsEV Level 2 home chargers, subpanels
4 AWG41,74085 AmpsLarge subpanels, solar inverter feeder lines
2 AWG66,360115 Amps100A main service distribution

Frequently Asked Questions

The American Wire Gauge (AWG) is the standardized wire gauge system used in North America for the diameters of round, solid, nonferrous, electrically conducting wire. Note that gauge numbers have an inverse relationship with wire size: a smaller AWG number represents a thicker wire with higher current capacity (e.g., 10 AWG is thicker than 14 AWG).

Voltage drop occurs due to the natural resistance of the copper wire. In a 120V household system, a 3V drop is only 2.5% (negligible). But in a 12V automotive, RV, or solar system, that same 3V drop represents a catastrophic 25% loss, causing inverters to shut down, LED lights to flicker, and pumps to burn out.

The National Electrical Code (NEC) recommends a maximum voltage drop of 3% for branch circuits feeding critical equipment (like solar inverters, navigation electronics, and medical gear), and 5% maximum total drop for non-critical circuits.

Resistance is directly proportional to wire length. Doubling the distance of your wire run doubles the electrical resistance and doubles the voltage drop. Therefore, longer runs require significantly thicker (lower AWG number) cables.

Copper has approximately 61% higher conductivity than aluminum, meaning a copper wire can be substantially thinner than an aluminum wire carrying the same current. Aluminum is primarily used for heavy residential service entrances and utility transmission because it is much lighter and cheaper.

This calculator asks for your ONE-WAY physical cable run distance. It automatically doubles the length internally for 2-wire DC and 1-phase AC systems to account for the return path.

Ampacity is the maximum current a wire can safely carry continuously without melting its insulation or causing a fire. Voltage drop is about efficiency and terminal performance. Sizing must satisfy BOTH safety ampacity and voltage drop limits.

Under US NEC standards: standard 15-amp 120V circuits use 14 AWG copper wire. Standard 20-amp kitchen, bathroom, and outdoor circuits require 12 AWG copper wire. 30-amp dryer/water heater circuits require 10 AWG copper wire.